1. Home
  2. Solutions
  3. Predictive maintenance
  4. Chiller monitoring

Chiller Monitoring in Qatar

kW per ton, approach temperatures and compressor health for every chiller in your plant room, read from each chiller's own controller and a few added sensors.

kW per ton, approach, compressor healthFor every chillerRead from the chiller controllerOver BACnet or ModbusEnergy cost of each faultIn QAR, per day

Last updated

An engineer checks a tablet beside a centrifugal chiller in a plant room
Illustration: chiller CH-02 before its condenser clean, with condenser approach and kW per ton above its baseline.

What is a chiller monitoring system?

A chiller monitoring system reads each chiller's own controller over BACnet or Modbus and adds sensors where the controller is blind. It tracks kW per ton, evaporator and condenser approach temperatures, compressor vibration and current, so it catches fouled tubes, low refrigerant and compressor wear while the chiller still holds its load.

Two numbers do most of the work. kW per ton is the electrical power a chiller draws for each ton of refrigeration (TR) it delivers; lower is better. Approach is the gap between refrigerant and water temperature in each heat exchanger. As tubes scale up, approach rises first and kW per ton follows.

Condenser approach is the condensing refrigerant temperature minus the leaving condenser water temperature. Evaporator approach is the leaving chilled water temperature minus the evaporating refrigerant temperature (Oxmaint). Kahramaa says air conditioning accounts for a significant share of Qatar's electricity use (Gulf Times), so a drifting chiller is a cost as well as a predictive maintenance risk.

What it catches on a chiller.

Each fault moves the readings in its own pattern. These are the ones we set alerts for first.

What it catches on a chiller.
FaultWhat Quoriam seesWhere the reading comes from
Condenser tube foulingCondenser approach creeping up at the same load, then kW per tonChiller controller
Low refrigerant or evaporator foulingEvaporator approach rising, supply water drifting above setpointChiller controller
Low condenser water flowHigh condenser approach with a small condenser water temperature differenceChiller controller and BMS pump status
Compressor bearing wearCompressor vibration rising against its own baselineVibration sensor; see vibration monitoring
Compressor motor strainMore amps for the same cooling loadChiller controller or clamp-on current sensors

What a healthy chiller should draw.

ASHRAE 90.1-2016, Table 6.8.1-3, provides a published benchmark for new water-cooled chillers at standard rating conditions. These edition-specific values are a reference, not a Qatar compliance requirement or an in-service target.

Maximum kW per ton for new water-cooled chillers, Path A, full load and IPLV
Chiller typeSizeFull loadIPLV
CentrifugalUnder 300 TR0.6100.550
300 to 400 TR0.5600.520
400 to 600 TR0.5600.500
600 TR and over0.5600.500
Screw and scrollPositive displacementUnder 150 TR0.720 to 0.7500.560 to 0.600
150 to 300 TR0.6600.540
300 TR and over0.560 to 0.6100.500 to 0.520

kW per ton of refrigeration; IPLV is the integrated part load value. A chiller in service runs at site conditions, so Quoriam compares each machine first with its own baseline at the same load. Source: ASHRAE 90.1-2016 addenda, Table 6.8.1-3, PDF page 72, Path A. Checked 18 November 2026. Both full-load and IPLV limits apply; centrifugal ratings require adjustment outside standard conditions.

How it works.

  1. Connect

    An edge gateway in the plant room reads each chiller's controller over BACnet/IP or Modbus, read-only: water temperatures, refrigerant conditions, compressor current and run status.

  2. Fill the gaps

    Where the controller is blind we add a vibration sensor on the compressor, clamp-on current sensors and pipe temperature sensors.

  3. Learn

    Quoriam learns each chiller's normal kW per ton and approach at each load, so a one-degree drift stands out from the weather.

  4. Alert and act

    The HVAC team gets the likely cause and the energy it is costing. The work order closes once the readings are back in band.

Isometric illustration: a motor and pump on the site layer, the Quoriam machine health screen above, and the decision layer on top

System view

For IT, OT and security reviewers: where the data goes, and how.

  1. On the chillerController points; vibration sensor on the compressor where needed
  2. In the plant roomEdge gateway on BACnet/IP or Modbus; LoRaWAN for added sensors
  3. NetworkSite LAN or cellular, encrypted and kept apart from the control network
  4. Quoriam platformOn your premises or cloud hosted in Qatar
  5. Your team and systemsApp, SMS and email alerts; work orders to your CMMS

What your team sees.

Efficiency, temperatures and the cost of each fault, per chiller.

Quoriam chiller performance screen for CH-02 showing 30 days of chilled water temperatures, condenser approach and kW per ton trends, energy lost in QAR and a before and after comparison with CH-01
Chiller performance. Supply water against its learned baseline over 30 days, condenser approach and kW per ton, the energy lost to fouling and a before-and-after comparison with CH-01.
Quoriam work order screen for chiller CH-02 with checklist, parts used, technician photos of the tube sheet and the supply water temperature back in band
Work order. Condenser tubes cleaned and charge checked, with the checklist, parts, photos and the close-out reading back in band.
Quoriam devices screen listing sensors, meters and controllers with protocol, signal, battery and last seen, including the CH-02 chiller controller on BACnet/IP
Devices. The CH-02 controller on BACnet/IP through the plant room gateway, listed with every wireless sensor and its signal and battery.

Or just ask.

Quoriam AI answers in plain language and turns the answer into an action.

Where it's used in Qatar.

Anywhere a chiller trip is felt within the hour.

  • Towers, malls and hotels

    Building plant rooms where tenants notice a warm afternoon before the BMS does.

    Facilities and smart buildings
  • District cooling plants

    Large centrifugal chillers where a small drift in kW per ton adds up fast.

    Utilities and district cooling
  • Hospitals

    Cooling for wards, theatres and stores that has to hold through the summer peak.

    Healthcare
  • Manufacturing

    Process cooling where warm chilled water slows the line or spoils the product.

    Manufacturing

Questions buyers ask.

Something else? Ask us during the free assessment.

What is a good kW per ton for a chiller?

ASHRAE 90.1-2016 Path A lists 0.560 kW per ton at full load for water-cooled centrifugal chillers of at least 300 TR at standard rating conditions; the paired IPLV limit also applies. See ASHRAE Table 6.8.1-3. In service, the better test is each chiller against its own baseline at the same load. A rise of a few hundredths is worth a look.

How do you detect chiller condenser fouling?

By watching condenser approach at the same load. Scale on the tubes stops heat getting from refrigerant to water, so approach rises, then kW per ton and compressor current follow. On the screen above, CH-02's approach went from about 2 K to 5.8 K before cleaning brought it back to 1.9 K.

How do you spot a refrigerant leak?

A low charge usually shows as a rising evaporator approach and supply water drifting above setpoint, though evaporator fouling and oil logging look similar, as Oxmaint notes. The alert asks the technician to check superheat and charge. A refrigerant detector in the plant room can alarm through the BMS too.

Can you read our chiller controllers?

Yes, over BACnet/IP or Modbus, through the BMS or straight from the chiller panel, wherever the controller offers either. We map the points with your BMS contractor and read them without changing the control logic or the chiller's settings.

What hardware does chiller monitoring need?

Often very little. One edge gateway per plant room reads the controllers. We add a vibration sensor on each compressor that matters, clamp-on current sensors where the controller doesn't report amps, and pipe temperature sensors where water temperatures aren't measured. The free assessment counts it for your plant.

Will Quoriam change our chiller setpoints?

No. Chiller monitoring is read-only. Your BMS and chiller controls keep running the plant; Quoriam watches it, alerts your team and raises the work order. Changing sequencing or setpoints stays with your controls team; see HVAC and energy optimisation.

What does chiller monitoring cost?

It depends on how many chillers you have and how each one connects. The free three-week assessment ends with a scope and a fixed price for your plant, and a pilot on your most critical chillers is available.

Find the chiller costing you most.

A free three-week assessment. We read your chiller and BMS data, rank each machine by efficiency and condition, and show where monitoring pays back first.

We take on two assessments a month.

Quoriam is designed to pay back within six months. How we calculate payback